American Power Conversion MX28B400 Power Supply User Manual


 
MX28B400 +24 VDC User’s Manual Page 29
Parameter Locations, Descriptions, and Default Values
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Lamp Test
Security Level {1}
[SYSTEM/DIAG]
Setting Lamp Test to “ON” will turn on
the “MAJOR”, “MINOR”, “NORMAL”,
“MAJ”, and “MIN” LEDs on the control
unit front panel.
Lamp Test m+
OFF
LVD 1 or 2 Option
Security Level {1}
[MODULES/LVD/SET-ALM]
Must be set to “Enable” if the unit has an
LVD. If the unit has an LVD, but it is
disabled, the controller will not
disconnect the LVD.
LVD Option m+
Disable
LVD 1 or 2 Reset
Security Level {1}
[MODULES/LVD/PARAM]
LVD Reset (reconnect) threshold voltage.
LVD Reset m+
+24.00 V
LVD 1 or 2 Trip
Security Level {1}
[MODULES/LVD/PARAM]
LVD Trip (disconnect) threshold voltage.
LVD Trip m+
+21.00 V
LVD Alarm
Security Level {1}
[MODULES/LVD/SET-ALM]
The output relay that is energized when
the controller opens the LVD. If unit has
a battery LVD, no power will be available
to turn on any Output Relays.
LVD Open Alm m+
Minor
Model Programming
Security Level {2}
[SYSTEM/SETUP]
Model type number for the power plant
NOTE: Changing the model number
causes the system to reinitialize.
Model m+
MX28B-400 +24V
OEM R Gain
Security Level {2}
[OEM]
Voltage gain adjustment for factory
calibration of system voltage
readings/settings.
OEM R Gain m+
1.000 V
OEM R Offset
Security Level {2}
[OEM]
Voltage offset adjustment for factory
calibration of system voltage
readings/settings.
OEM R Offset m+
0.000 V
OEM S Gain
Security Level {2}
[OEM]
Current gain adjustment for factory
calibration of battery current
readings/settings.
OEM S Gain m+
1.000 A
OEM S Offset
Security Level {2}
[OEM]
Current offset adjustment for factory
calibration of battery current
readings/settings.
OEM S Offset m+
0.0 A
Output Relay 1 Alarm
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
Output Relay 6 Alarm
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
Output Relay 1 Alarm can be “mapped”
to activate other output relays (“Ignore”
activates no additional relays).
Output Relay 6 Alarm can be “mapped”
to activate other output relays (“Ignore”
activates no additional relays).
Out-Rly 1 Alm m+
Ignore
Out-Rly 6 Alm m+
Ignore