American Power Conversion MX28B400 Power Supply User Manual


 
MX28B400 +24 VDC User’s Manual Page 31
Parameter Locations, Descriptions, and Default Values
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Rectifier Current Limit Alarm
Security Level {1}
[MODULES/RECT/SET-ALM]
The output relay that is energized or
special rectifier alarm group n of N that
occurs when a rectifier has been forced
into the current limited mode.
Rect CL Alm m+
n of N
Rectifier Current Limit Alarm
Status
{Status Only}
[MODULES/RECT/INFO]
The status will be “ON” if the rectifier has
been forced into its current limited mode.
NOTE
: This information can be
viewed for each rectifier installed by
using the horizontal arrow keys.
Rect 1 CL #
OFF
Rectifier Current Output Status
{Status Only}
[MODULES/RECT/INFO]
A display of the dc output current for the
individual rectifier. NOTE
: This
information can be viewed for each
rectifier installed by using the
horizontal arrow keys.
Rect 1 Curr #
24.9 A
Rectifier Description
{Status Only}
[MODULES/RECT/INFO]
Displays the model number of the
installed rectifier. NOTE
: This
information can be viewed for each
rectifier installed by using the
horizontal arrow keys.
Rect 1 Desc #
MRF28H27
Rectifier Fail 1-of-N Alarm
Security Level {1}
[SYSTEM/SET-ALM]
The output relay energized if Rectifier
Fail 1-of-N alarm occurs. This is a
special rectifier alarm group that signifies
that one rectifier has at least one alarm
condition.
Rect 1ofN Almm+
Minor
Rectifier Fail 2-of-N Alarm
Security Level {1}
[SYSTEM/SET-ALM]
The output relay energized if Rectifier
Fail 2-of-N alarm occurs This is a special
rectifier alarm group that signifies that
more than one rectifier has at least one
alarm condition.
Rect 2ofN Almm+
Major
Rectifier Fail Safe Voltage
Security Level {1}
[MODULES/RECT/PARAM]
Rectifier default output voltage if
communication with the control unit fails.
Rect Fail Safem+
+27.00 V
Rectifier Fan Fail Alarm
Security Level {1}
[MODULES/RECT/SET-ALM]
The output relay that is energized or
special rectifier alarm group n of N that
occurs when a rectifier fan has failed.
Rect FF Alm m+
n of N
Rectifier Fan Fail Alarm Status
{Status Only}
[MODULES/RECT/INFO]
The status will be “ON” if the rectifier fan
has failed. NOTE
: This information
can be viewed for each rectifier
installed by using the horizontal arrow
keys.
Rect 1 FF #
OFF
Rectifier Fault Alarm (RFA)
Status
{Status Only}
[MODULES/RECT/INFO]
The status will be on if the rectifier output
has failed. NOTE: This information
can be viewed for each rectifier
installed by using the horizontal arrow
keys.
Rect 1 RFA #
OFF
Rectifier RFA Alarm
Security Level {1}
[MODULES/RECT/SET-ALM]
The output relay that is energized or
special rectifier alarm group n of N that
occurs when a rectifier output has failed.
Rect RFA Alm m+
n of N