American Power Conversion SYMSTRF3I Power Supply User Manual


 
Page 2 - Electrical Installation
990-7166-001
Electrical Requirements
artemmyS
MT
tnenopmoC
gniriW
egatloV
)CAV(
tnerruC
daoLlluF
tnerrucrevO
noitcetorP
)lanretxE(
muminiM
eziSeriW
lanoitanretnI
ledoM1:3
I3FRTSMYS
tupnI
ssapyBhtiw
remrofsnarT
,V004,V083
V514ro
nehwesahP/A62
noA05,enilno
ni2Ldna1L
ssapyb
eloP-3pmA06mm01(GWA8#
2
)
tupnI
ssapyBtuohtiw
remrofsnarT
nehwesahP/A62
noA08,enilno
ssapybni1L
eloP-3pmA001mm52(GWA3#
2
)
tuptuO
,V032,V022
V042ro
A08eloP-1pmA001mm52(GWA3#
2
)
ssapyB
gnicnalaB
remrofsnarT
tupnI
.emarfmetsysybdellortnoC
mm01(GWA8#
2
*)
tuptuO mm52(GWA3#
2
*)
artemmySehtmorf)m51('05nahtrehtrufonremrofsnartgnicnalabssapybehtllatsnI*
MT
.
.eguageriwgnitcelesnehwpordegatlovnirotcaf,deriuqersiecnatsidretaergafI
EPO Switch Wiring (Required)
The Symmetra
TM
Power Array is to be connected to either a dry contact or 24Vdc Emergency Power Off (EPO)
switch. The terminal connections for the EPO switch are physically isolated from the primary circuitry of the
Power Array system.
EPO Specifications
The EPO circuit is considered a Class 2 and SELV circuit.
SELV is an acronym for “Safety Extra Low Voltage.” SELV is a common term in Europe and IEC standards. A
SELV circuit is isolated from primary circuitry through an isolating transformer and designed so that under
normal conditions, the voltage is limited to 42.4 Vpeak or 60 Vdc.
A Class 2 Circuit is a common term in North America and in UL and CSA standards. It is defined in the Canadian
Electrical Code (C22.1, Section 16) and in the National Electrical Code (NFPA 70, Article 725).
SELV and Class 2 circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO
terminal block unless it can be confirmed that the circuit is SELV or Class 2. If there is a question, use a contact
closure switch. Use one of the following cable types to connect the Symmetra
TM
to the EPO switch:
CL2 - Class 2 cable for general purpose use.
CL2P - Plenum cable for use in ducts, plenums, and other space used for environmental air.
CL2R - Riser cable for use in a vertical run in a shaft or from floor to floor.
CL2X - Limited Use cable for use in dwellings and for use in raceway.
For installation in Canada, the cable should be CSA Certified, type ELC (Extra-Low-Voltage Control Cable).