American Power Conversion SYMSTRF3I Power Supply User Manual


 
Appendix C - Module Replacement - Page 3
990-7171-001
Battery Module Replacement
1. Remove the appropriate grill cover. The battery module bays are labeled on the center spine behind the grill
covers.
2. Battery modules are designed with a “drop lock” that holds them securely in the frame. Slightly lift the front
handle of the battery module, and pull it forward to the safety stop.
3. With one person on either side of the battery module, lift and remove the battery module from the frame.
Note: The safety stop retaining flange passes through the notch in the frame as the battery module is removed.
4. To dispose of the battery module, return it to the appropriate service provider or directly to APC for recycling.
Note: The battery module contains sealed, non-spillable lead acid batteries. These must be recycled or disposed of
properly.
5. Install the replacement battery module.
Replacement Battery Module Verification
From the startup screen, press any key to open the top level menu screen. Follow the sequence below to ensure
that the new battery module is recognized by the Power Array system and is functioning properly. (Status: OK).
n The 120V, 7.2 Ah battery module constitutes a risk of electrical shock and an energy hazard. High short
circuit current through conductive materials could cause severe burns. Before handling battery mod-
ules, remove conductive jewelry such as chains, wrist watches and rings.
n Battery modules weigh approx. 60 lb (27 kg). Two people are required to handle battery modules.
Warning!