APC AP8941 Power Supply User Manual


 
Switched Rack PDU User Guide31
Device Command Descriptions
Network Port Sharing Commands
The Command Line Interface allows commands to be sent to guest Rack PDUs. The user may specify
the Display ID of the Rack PDU to be commanded, followed by a colon, before the first argument (or as
the first argument, if the command does not normally have arguments). Providing a Display ID is
optional, omitting it will simply command the local Rack PDU. For example:
<command> <id>:<arg1> <arg2>
This will send <command> to the Rack PDU with the Display ID <id>. <id> is delimited from <arg1>
with a colon character; do not include any spaces between <id>:<arg1>, as spaces are used to delimit
arguments.
bkLowLoad
Access: Administrator, Device User
Description: Set or view the bank low-load threshold current in amps. You can specify all banks, a
single bank, a range, or a comma-separated list of single banks and/or ranges.
Example 1: To set the low-load threshold for all banks to 1A, type:
apc> bkLowLoad all 1
E000: Success
Example 2: To view the low-load threshold setting for banks 1 through 3, type:
apc> bkLowLoad 1-3
E000: Success
1: 1 A
2: 1 A
3: 1 A
Example 3: To view the low-load threshold setting for banks 1 and 2 on guest Rack PDU 3, type:
apc> bkLowLoad 3:1-2
E000: Success
1: 0 A
2: 0 A
bkNearOver
Access: Administrator, Device User
Description: Set or view the bank near-overload threshold current in amps. You can specify all banks, a
single bank, a range, or a comma-separated list of single banks and/or ranges.
Example 1: To set the near-overload threshold for all banks to 10A, type:
apc> bkNearOver all 10
E000: Success
Example 2: To view the near-overload threshold setting for banks 1 through 3, type:
apc> bkNearOver 1-3
E000: Success
1: 10 A
2: 10 A
3: 10 A
Example 3: To view the near-overload threshold setting for banks 1 and 2 on guest Rack PDU 3, type:
apc> bkNearOver 3:1-2
E000: Success
1: 16 A
2: 16 A