APC AP8941 Power Supply User Manual


 
34Switched Rack PDU User Guide
devReading
Access: Administrator, Device User
Description: View the total power in kilowatts or total energy in kilowatt-hours for the device.
Example 1: To view the total power, type:
apc> devReading power
E000: Success
5.2 kW
Example 2: To view the total energy, type:
apc> devReading energy
E000: Success
200.1 kWh
Example 3: To view the total power for guest Rack PDU 3, type:
apc> devReading 3:power
E000: Success
4.2 kW
devStartDly
Access: Administrator, Device User
Description: Set or view the amount of time in seconds, which is added to each outlet’s Power On
Delay before the outlet will turn on after power is applied to the Switched Rack PDU. Allowed values
are within the range of 1 to 300 seconds or never (never turn on).
Example 1: To view the cold start delay, type:
apc> devStartDly
E000: Success
5 seconds
Example 2: To set the cold start delay to six seconds, type:
apc> devStartDly 6
E000: Success
Example 3: To set the cold start delay to six seconds on guest Rack PDU 2, type:
apc> devStartDly 2:6
E000: Success
Example 4: To view the cold start delay on guest Rack PDU 2, type:
apc> devStartDly 2:
E000: Success
6 sec
Argument Definition
power View the total power in kilowatts.
energy View the total energy in kilowatt-hours.