Switched Rack PDU User Guide33
devLowLoad
Access: Administrator, Device User
Description: Set or view the low-load threshold in kilowatts for the device.
Example 1: To view the low-load threshold, type:
apc> dev
E000: Success
0.5 kW
Example 2: To set the low-load threshold to 1 kW, type:
apc> dev 1.0
E000: Success
Example 3: To set the low-load threshold to 1.5 kW on guest Rack PDU 3, type:
apc> devLowLoad 3:1.5
E000: Success
devNearOver
Access: Administrator, Device User
Description: Set or view the near-overload threshold in kilowatts for the device.
Example 1: To view the near-overload threshold, type:
apc> devNearOver
E000: Success
20.5 kW
Example 2: To set the near-overload threshold to 21.3 kW, type:
apc> devNearOver 21.3
E000: Success
devOverLoad
Access: Administrator, Device User
Description: Set or view the overload threshold in kilowatts for the device.
Example 1: To view the overload threshold, type:
apc> devOverLoad
E000: Success
25.0 kW
Example 2: To set the overload threshold to 25.5 kW, type:
apc> devOverLoad 25.5
E000: Success
Example 3: To view the overload threshold for guest Rack PDU 3, type:
apc> devOverLoad 3:
E000: Success
5.0 kW