APC none Network Card User Manual


 
Network Management Card User’s Guide 33
Device Manager Menus
UPS Control
Overview
The table below describes the
Control
menu options you can use with
all UPS models except a Silcon DP300E series UPS. When you select
an option, a description of what will occur, and when, is provided as part
of a confirmation process. You can then chose to initiate the selected
action, or cancel it, based on that description.
Note: For descriptions of the
Self-Test
,
Simulate Power Failure
,
Start/
Stop Runtime Calibration
, and
Test UPS Alarm
options, which
are
Control
menu options in the Control Console, see
Diagnostics on page 31.
$FWLRQ 'HILQLWLRQ
Turn UPS On
(Control Console
only)
Turns on power at the UPS when a software command was
used to turn off output power. If the on/off switch at the UPS
was used to turn off power, that switch must be used to turn on
power.
Turn UPS Off
1
Turns off power after the Shutdown Delay until you turn on
power again.
Turn UPS Off
Gracefully (Control
Console)
2
Turns off power after two delays: A delay (Maximum
Shutdown Time plus two minutes) that allows time for
PowerChute to safely shut down its server, and the Shutdown
Delay.
Reboot UPS
1
Reboots the attached equipment by doing the following:
Turns off power at the UPS
after the Shutdown Delay.
Turns on power at the UPS after the Return Delay.
Reboot UPS
Gracefully (Control
Console)
2
Reboots the attached equipment by doing the following:
Turns off power after two delays: A delay (Maximum
Shutdown Time plus two minutes) that allows time for
PowerChute to safely shut down its server, and the
Shutdown Delay
Turns on power after the Return Delay.
Put UPS To Sleep
1
Puts the UPS into its sleep mode (turns off power for a defined
period of time), as follows:
Turns off power after the Shutdown Delay.
Turns on power after two delays: Sleep Time and Return
Delay.
Put UPS To Sleep
Gracefully (Control
Console)
2
Puts the UPS into its sleep mode (turns off power for a defined
period of time), as follows:
Turns off power after two delays: A delay (Maximum
Shutdown Time plus two minutes) that allows time for
PowerChute to safely shut down its server, and the
Shutdown Delay.
Turns on power after two delays: Sleep Time and Return
Delay.
Put UPS In/Take
UPS Off Bypass
Controls the use of the bypass, an operational mode that allows
maintenance to be performed at a Matrix-UPS or Symmetra
UPS without turning off power at that
UPS
.
1
The Web Interface has a
Signal servers
option. When
Yes
is selected for that
option, initiating an action is equivalent to selecting the Control Console’s
Turn UPS
Off Gracefully
,
Reboot UPS Gracefully
, or
Put UPS To Sleep Gracefully
options.