Magnum VS –48 Vdc User’s Manual Page 6
Rectifier Terminal # Function Terminal # Function Terminal # Function
Rectifier 1 TRM2 Ground TRM5 Line or Neutral TRM8 Line
Rectifier 2 & 3 TRM3 Ground TRM6 Line or Neutral TRM9 Line
Rectifier 4 & 5 TRM4 Ground TRM7 Line or Neutral TRM10 Line
Chassis TRM1 Ground
Figure 3.3-3 AC Input Wiring
AC Power Cord Sets
AC input cable kits are available from APC. These cables are 12 feet (3.7m) long and have a
power plug installed on each cable. When ordered with the power system, these cables will be
installed with strain reliefs provided to mount the 3-conductor jacketed cables. Each kit will
supply power to the entire power system. Use the chart in Figure 3.3-5 to determine the
suggested cable kits.
Part Num. AWG Cable Qty Plug Num. Plug Style Voltage Power System
0M-91157 14 3 NEMA 5-15 Non-locking 115 Magnum VS 50
0M-91155 14 3 NEMA L5-15 Locking 115 Magnum VS 50
0M-91156 12 2 NEMA 5-20P Non-locking 115 Magnum VS 50
0M-91154 12 2 NEMA L5-20P Locking 115 Magnum VS 50
0M-91158 10 1 NEMA 5-50P Non-locking 115 Magnum VS 50
0M-1150 12 2 NEMA L6-20P Locking 230 Magnum VS 50
0M-91160 10 1 NEMA 6-30P Non-locking 230 Magnum VS 50
0M-91159 10 1 NEMA L6-30P Locking 230 Magnum VS 50
0M-91137 12 6 NEMA 5-15P Non-Locking 115 Magnum VS 100
0M-91140 12 6 NEMA L5-15P Locking 115 Magnum VS 100
0M-91138 12 4 NEMA 5-20P Non-locking 115 Magnum VS 100
0M-91141 12 4 NEMA L5-20P Locking 115 Magnum VS 100
0M-91139 10 2 NEMA 5-50P Non-locking 115 Magnum VS 100
0M-1149 12 4 NEMA L6-20P Locking 230 Magnum VS 100
0M-91135 10 2 NEMA 6-30P Non-locking 230 Magnum VS 100
0M-91136 10 2 NEMA L6-30P Locking 230 Magnum VS 100
Figure 3.3-5 Power Cord Sets
WARNING: Hazardous ac voltage levels are present inside the power
system. Keep the rear cover in place when the system is operational or
energized.
The rear cover of each shelf in the power system is provided with two 1.125-inch (2.858 cm)
diameter holes for electrical conduit. Conduit can be run to each shelf or strain reliefs are
provided to install jacketed cables.