Magnum VS –48 Vdc User’s Manual Page 30
Figure 6.4-1 Parameter Locations, Descriptions, and Default Values
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION SETTINGS (Default
Settings in BOLD)
Alarms Item 1
{Status Only}
[ALARMS]
[告警]
Display of up to 16 active alarms. Scroll
up or down to select individual alarms.
Alarm Status Only
Battery Capacity
[SETUP/BATTERY/
CAP]
[设置 / 电池 / 容量]
The total battery capacity in ampere-
hours of the entire battery array.
Normally specified at 20 hour discharge
rate.
0Ah – 10,000 Ah, 0 Ah
Battery Current
{Status Only}
[STATUS/BATTERY/
PARAMETERS]
[状态 / 电池 / 参数]
Battery current measured by the system
controller at the battery current shunt.
Battery Current Status
Only
Battery Float Voltage
[SETUP/BATTERY/
VOLTAGE/FLOAT]
[设置 / 电池 / 电压 /
浮充]
One of three parameters that control the
dc output voltage. Set the Float Voltage
to the desired 25°C battery temperature
per the battery manufacturers
recommendations.
-56.5V - -47.0V, -54.00 V,
Battery Functional Test
[SETUP/BATTERY/TEST]
[设置 / 电池 / 测试]
Lowers the system voltage so a
discharge test of the battery is
performed. ON – initiates a battery test.
Off – stops a test in progress.
ON, OFF
Battery Functional Test Result
[STATUS/BATTERY/TEST]
[状态 / 电池 / 测试]
Displays the results of the last battery
test.
FAIL, PASS,
INTERRUPTED, IN
PROCESS, NOT
PERFORMED
Battery Maximum Recharge
Current
[SETUP/BATTERY/CURRENT]
[设置 / 电池 / 电流]
One of three parameters that control the
dc output voltage. If Battery Current
surpasses the Maximum Battery
Recharge Current, the dc output voltage
will be reduced (the system limits the
charging current to this programmable
value).
0 – 500 A, 5 A
Battery Mode Status
[STATUS/BATTERY/MODE]
[状态 / 电池 / 模式]
This will display the condition of the
battery. Float is normal operation.
Discharge means the rectifiers are not
producing enough current and the
batteries are discharging. Equalizing
means the voltage is above float voltage
to give the batteries an equalize charge.
Float, Equalizing or
Discharge.