APC VS 100 Power Supply User Manual


 
Magnum VS –48 Vdc User’s Manual Page 39
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION SETTINGS (Default
settings in BOLD)
Battery Max Recharge
{Status Only}
[System/DC Parameters]
This is just a convenient place to view
the Battery Max Recharge Current
parameter. Go to Batteries/Parameters
to change setting.
Status Only
Battery Maximum Recharge
Current
[Batteries/Parameters]
One of three parameters that control the
dc output voltage. If Battery Current
surpasses the Maximum Battery
Recharge Current, the dc output voltage
will be reduced (the system limits the
charging current to this programmable
value).
0 – 10,000 A, 10 A
Battery Temperature
[System/DC Parameters]
Battery temperature measured by the
system controller at the optional battery
temperature sensor probe.
Status Only
Battery Temperature
Compensation High Knee
[Batteries/Parameters]
The temperature compensation high
knee is the point where there is no
additional battery voltage compensation
for further increases in temperature.
0 °C – 100 °C, 40.0 °C
Battery Temperature
Compensation Low Knee
[Batteries/Parameters]
The temperature compensation low knee
is the point where there is no additional
battery voltage compensation for further
decreases in temperature.
-100 °C – 100 °C, 0.0 °C
Battery Temperature
Compensation Method
[Batteries/Parameters]
One of three parameters that control the
dc output voltage. Activate “ON” or de-
activate “OFF” battery temperature
compensation.
ON, OFF
Battery Temperature
Compensation Temperature
Coefficient
[Batteries/Parameters]
Temperature compensation coefficient
between low knee and high knee in
mV/cell/°C. (Compensation equals zero
at 25°C.)
-4.99 mV – 0 mV,
-3.00mV
Circuit Breaker 1 Alias
[Distribution/Breakers]
Circuit Breaker 4 Alias
[Distribution/Breakers]
An alternate name (alias) can be
assigned to Circuit Breaker 1 if desired.
This feature is supported by the standard
SNMP card monitor, but is not supported
by this dc system.
Circuit Breaker 1
Circuit Breaker 4
Circuit Breaker 1 Tripped
[Distribution/Breakers]
Circuit Breaker 4 Tripped
[Distribution/Breakers]
Defines the output relay that is energized
when Circuit Breaker 1 is tripped.
Defines the output relay that is energized
when Circuit Breaker 4 is tripped.
Ignore, Minor, Major
Output Relay 1-6
Ignore, Minor, Major
Output Relay 1-6
Circuit Breaker 5-72 is not
used in this system.
Communications Fail
Defines the output relay that is energized
if the System stops communicating with
the rectifiers. This feature is supported
by the standard SNMP card monitor, but
is not supported by this dc system.
Ignore, Minor, Major
Output Relay 1-6•