Magnum VS –48 Vdc User’s Manual Page 45
the system and the bus voltage reaches the level defined by the LVD 1 Reset Voltage variable.
The LVD control can be disabled on the LVD parameters screen in the controller.
The LVD will not be energized until a battery string is installed with the correct polarity and the
battery disconnect switch is turned on. This will prevent the battery from being hooked up
backwards and damaging the rectifiers and/or the loads. Once the battery is connected
correctly and the LVD is closed, the LVD will open only in low voltage situations. The battery
connections are to be used for the battery only.
6.10. Programming Output Relays
Any alarm condition such as System High Voltage Alarm, Battery Discharge Alarm or Rectifier 1
of n Alarm can be programmed to any of the eight output relays. Programming alarms to the
output relays 1-6 will give a much better idea of what the failure is before actually visiting the
site. Using the default programming, over twenty conditions could cause activate a minor relay.
However, if you program Battery Discharge Alarm to Output Relay 1, you will know exactly what
the alarm is just by knowing that output relay 1 is on. The network management card also
displays the output relays individually and can be set up to e-mail these messages.
Output relay mapping options are Ignore, Major, Minor and Output Relay 1-6. To program the
alarm to an output relay find the alarm setup screen for the desired alarm from the table in
Figure 6.8-1. The Ignore setting will not send an alarm to any display or relay. Programming
the alarm to Major, Minor or Output Relay 1 will send the alarm to the relay output connector on
the back of the plant, turn on the appropriate front panel LED, and will send the alarm to the
network management card. Programming the alarm to Output Relay 2-6 will not send the alarm
to the relay output connector on the back of the plant, but will turn on the front panel Out Relay
LED, and will send the alarm to the network management card. For instance, go to the
Batteries / Parameters screen and program Battery Discharge Alarm to Output Relay 1. When
the battery discharge current goes above the default setting of 5 Amps, the alarm will come on,
the Out Relay contact will energize, the front panel Out Relay LED will come on and the network
management card will report Output Relay 1 is on.
Most alarms are originally assigned to a minor or major relay. Usually it is desirable to keep the
minor and major assignments when programming to the output relays. To do this, go to the
output relay-programming screen and map the relay back to the desired minor or major relay.
For instance, go to the I/O / Output screen and program Relay 1 to Minor Relay. When the
battery discharge current goes above the default setting of 5 Amps, the alarm will come on, the
Out Relay contact will energize, the Out Relay LED will come on and the network management
card will report Output Relay 1 is on. In addition, the Minor Relay contact will energize, the front
panel Minor LED will come on and the network management card will report the Minor Relay is
on. With this scheme of programming, you will know that you have a minor alarm and
specifically that the batteries are discharging.
Out Relay 1-6 can be renamed using the Relay Alias setup screen. Each relay name can be up
to sixteen characters in length. This name will not appear in the alarm summary, but will appear
in the messages generated by the network management card. This can be used to give specific