APC VS 100 Power Supply User Manual


 
Magnum VS –48 Vdc User’s Manual Page 42
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION SETTINGS (Default
settings in BOLD)
Low Temperature Threshold
[System/DC Parameters]
System Temperature is ambient
temperature measured inside the
controller. An alarm will be reported if
temperature is lower than the
temperature entered. Not the same as
battery temperature threshold.
-100 °C – 100 °C, 0.0 °C
Low Voltage Alarm
[Power Modules/Rectifiers]
Defines the output relay that is energized
if the System Voltage is below the
System Low Voltage threshold. Not the
same as battery voltage alarm.
Ignore, Minor, Major
Output Relay 1-6
Low Voltage Threshold
[Power Modules/Rectifiers]
System Voltage is bus voltage measured
by the controller. An alarm will be
reported if voltage is lower than the
voltage entered. Not the same as battery
voltage threshold.
-60 V – -40 V, -50.00 V
LVD 1 Option
[Batteries/LVD]
If the unit has an LVD, but it is disabled,
the controller will not disconnect the LVD.
Enable, Disable
LVD 1 Reset
[Batteries/LVD]
LVD Reset (reconnect) threshold voltage. -56 V – -40 V, -50.00 V
LVD 1 Trip
[Batteries/LVD]
LVD Trip (disconnect) threshold voltage. -56 V – -40 V, -42.00 V
LVD 2 Option
[Batteries/LVD]
Not available on this system.
Disable
LVD 2 Reset
[Batteries/LVD]
Not available on this system. 0.00 V
LVD 2 Trip
[Batteries/LVD]
Not available on this system. 0.00 V
LVD Alarm
[Batteries/LVD]
Defines the output relay that is energized
when the controller opens the LVD. If
unit has a battery LVD, no power will be
available to turn on any Output Relays.
Ignore, Minor, Major
Output Relay 1-6
Output Relay 1 Alarm
[I/O/Output]
Output Relay 1 Alarm can be “mapped”
to activate other output relays (“Ignore”
activates no additional relays).
Ignore, Minor, Major
Output Relay 1-6
Output Relay 2 Alarm
[I/O/Output]
Output Relay 6 Alarm
[I/O/Output]
Output Relay 2-6 Alarm can be “mapped”
to activate other output relays (“Ignore”
activates no additional relays). Alarms
that are mapped to output relay 2-6 are
not supported by hardware. The network
management card supports programming
these relays. These relays can be
mapped to the hardware relays minor
and major.
Ignore, Minor, Major
Output Relay 1-6
Ignore, Minor, Major
Output Relay 1-6