APC VS 100 Power Supply User Manual


 
Magnum VS –48 Vdc User’s Manual Page 32
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION SETTINGS (Default
Settings in BOLD)
Equalization Duration
[SETUP/BATTERY/
VOLTAGE/EQUALIZATION/
DURATION]
[设置 / 电池 / 电压 /
均充 / 均充时间]
This setting defines the number of hours
the batteries will be equalized in all
methods of equalization. During the
initial stage of equalization the batteries
will have to be increased to the
equalization voltage. Once the battery
voltage and current meet equalization
parameters, the equalization duration
timer will start.
00 HOURS- 24 HOURS,
0 HOURS
Equalize Manually
[SETUP/BATTERY/
VOLTAGE/EQUALIZATION/
METHOD/MANUAL]
[设置 / 电池 /电压 /
均充 / 模式 /手动]
Applies an overcharge to the battery to
equalize the specific gravity of a battery.
Manual equalization is a one-time
equalization process. The operator turns
on manual equalization each time he
wishes an unscheduled equalization to
occur. To abort an automatic or periodic
equalization in progress, turn manual
equalization ON and then OFF.
ON, OFF
Equalize Periodically
[SETUP/BATTERY/
VOLTAGE/EQUALIZATION/
METHOD/PERIODIC]
[设置 / 电池 /电压 /
均充 / 模式 /周期]
Applies an overcharge to the battery to
equalize the specific gravity of a battery.
Periodic equalization is equalization after
a set number of days.
ON, OFF;
0-180 Days, 180 Days
Equalization Voltage
[SETUP/BATTERY/
VOLTAGE/EQUALIZATION/
VOLTAGE]
[设置 / 电池 / 电压 /
均充 / 电压]
The overcharge voltage that will be
applied to the battery
-56.5 V - -48.0 V, -56.0 V
Language Selection The screen will revert to the language
selection screen after a reset. Choices
are English and Chinese.
Pin Entry
[SETUP]
[设置]
Enter PIN to access setup menus.
Entering setup brings you to the PIN
entry screen. In-activity for two minutes
will de-activate system access.
0000 – 9999, 2222
PIN Setup
[SETUP/SYSTEM/SET PIN]
[设置 / 系统 / 码设置]
Change PIN that the user will use to log
on to the system. If you change the PIN,
Do Not Forget It.
0000 – 9999, 2222
Rectifier Current Limit Status
{Status Only}
[STATUS/RECT]
[ 状态 / 模块]
A display of the current limit alarm for the
individual rectifier. Scroll up or down to
select individual rectifiers.
Rectifier Current Limit
Status Only