Magnum VS –48 Vdc User’s Manual Page 38
Figure 6.8-1 Parameter Locations, Descriptions, and Settings
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION SETTINGS (Default
settings in BOLD)
Alarms Item 1
{Status Only}
[System/Active Alarms]
•
•
•
Alarms Item 16
[System/Active Alarms]
Display of up to 16 active alarms (a
typical alarm screen is shown).
•
•
•
Display of up to 16 active alarms (a
typical alarm screen is shown).
No Alarms
•
•
•
No Alarms
Battery Current
{Status Only}
[System/DC Parameters]
Battery current measured by the system
controller at the battery current shunt.
Status Only
Battery Discharge Alarm
[Batteries/Parameters]
Defines the output relay that is energized
if the battery discharge current exceeds
the programmed battery discharge
threshold.
Ignore, Minor, Major
Output Relay 1-6
Battery Discharge Threshold
[Batteries/Parameters]
An alarm is generated if the battery
discharge current exceeds this value.
0 A – 20A, 5 A
Battery Float Voltage
[Batteries/Parameters]
One of three parameters that control the
dc output voltage. Set the Float Voltage
at 25°C battery temperature per the
battery manufacturers recommendations.
-56.5 – -47.0, -54.00 V
Battery High Temperature
Alarm
[Batteries/Parameters]
Defines the output relay that is energized
if the battery temperature exceeds the
Battery High Temperature threshold.
Ignore, Minor, Major
Output Relay 1-6
Battery High Temperature
Threshold
[Batteries/Parameters]
Battery Temperature is temperature
measured at the battery probe. An alarm
is generated if the battery temperature
exceeds this value.
-100 °C – 200 °C, 40.0 °C
Battery High Voltage Alarm
[Batteries/Parameters]
Defines the output relay that is energized
if the dc output voltage rises above the
battery high voltage threshold.
Ignore, Minor, Major
Output Relay 1-6
Battery High Voltage Threshold
[Batteries/Parameters]
An alarm will be reported if temperature
is lower than the temperature entered.
An alarm is generated if the dc output
voltage rises above this value.
-40.00 V – -60.00 V, -
58.00 V
Battery Low Temperature
Alarm
[Batteries/Parameters]
Defines the output relay that is energized
if the Battery Temperature drops below
the battery Low Temperature threshold.
Ignore, Minor, Major
Output Relay 1-6
Battery Low Temperature
Threshold
[Batteries/Parameters]
Battery Temperature is temperature
measured at the battery probe. An alarm
is generated if the battery temperature
drops below this value.
-100 °C – 200 °C, -20.0
°C
Battery Low Voltage Alarm
[Batteries/Parameters]
Defines the output relay that is energized
if the dc output voltage drops below the
battery low voltage threshold.
Ignore, Minor, Major
Output Relay 1-6
Battery Low Voltage Threshold
[Batteries/Parameters]
An alarm is generated if the dc output
voltage drops below this value.
-40.00 V – -60.00 V,
-44.00 V