Magnum VS –48 Vdc User’s Manual Page 55
Magnum VS 50 Power System
Output Voltage (factory
programmed)
54.0 Vdc
Operating Voltage Range 47 – 56.5 Vdc
Rated Output Current 50 A
Efficiency 85% Typical
Over Voltage Protection 59.5 Vdc
Output Current 45 A Minimum Continuous at 115 Vac Input
52.5 A Minimum Continuous at 230 Vac Input.
Current Limit 46.5 A Maximum at 115 Vac Input
55.0 A Maximum at 230 Vac Input.
Power Output @ 54.5 Vdc 2450 W Continuous at 115 Vac Input
2850 W Continuous at 230 Vac Input
Magnum VS 100 Power System
Output Voltage (factory
programmed)
54.0 Vdc
Operating Voltage Range 47 – 56.5 Vdc
Rated Output Current 100 A
Efficiency 91% Typical
Over Voltage Protection 59.5 Vdc
Output Current 90 A Minimum Continuous at 115 Vac Input
105 A Minimum Continuous at 230 Vac Input.
Current Limit 93 A Maximum at 115 Vac Input
110 A Maximum at 230 Vac Input.
Power Output per Rectifier
@ 54.5Vdc
4900 W Continuous at 115 Vac Input
5700 W Continuous at 230 Vac Input