Magnum VS –48 Vdc User’s Manual Page 31
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION SETTINGS (Default
Settings in BOLD)
Battery Temperature
[STATUS/BATTERY/
PARAMETERS]
[状态 / 电池 /参数]
Battery temperature measured by the
system controller at the optional battery
temperature sensor probe.
Battery Temperature
Status Only
Date Setup
[SETUP/SYSTEM/TIME/DATE]
[设置 / 系统 / 时/日]
System date stored in the controller.
Used as a date stamp in the event log.
Current DATE
Date Status
[STATUS/SYSTEM/Time/Date]
[状态 / 系统 / 时/日]
Displays the current controller date. Date Status Only
Equalize Automatically On/Off
[SETUP/BATTERY/
VOLTAGE/EQUALIZATION/
METHOD/AUTO]
[设置 / 电池 /电压 /
均充 / 模式 / 自动]
Applies an overcharge to the battery to
equalize the specific gravity of a battery.
Auto equalization is initiated when the
controller determines that the batteries
have been discharged a set percentage
of their capacity or the batteries have
been on discharge for a set duration.
Use this screen to turn auto equalization
on.
ON, OFF
Equalize Automatically on AC
Fail
[SETUP/BATTERY/
VOLTAGE/EQUALIZATION/
METHOD/AUTO/AC
FAIL/ON/OFF]
[设置 / 电池 /电压 /
均充 / 模式 / 自动
/自动]
Sets the time the ac input power has to
be off before equalization occurs.
15 MINUTES – 360
MINUTES, 15 MINUTES
Equalize Automatically on
Battery Discharge
[SETUP/BATTERY/
VOLTAGE/EQUALIZATION/
METHOD/AUTO/DISCHARGE]
[设置 / 电池 /电压 /
均充 / 模式 / 自动 /
交流故障]
Sets the percent of battery discharge
before equalization occurs. Percent
Discharge = Discharged ampere-hours /
Battery Capacity ampere-hours
5% - 50%, 30 %