Emerson 582145500 Power Supply User Manual


 
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
6
Section 6040
Model: NetSure™ ITM Issue AB, April 8, 2013
2.0 I
NSTALLATION
D
RAWINGS
AND
R
ECOMMENDED
T
OOLS
AND
T
EST
E
QUIPMENT
2.1 Installation Drawings
The diagrams in this section illustrate the key mechanical and electrical characteristics of the
NetSure ITM DC UPS system.
General Notes Applicable to All Illustrations
1. All dimensions are in inches (millimeters).
2. Minimum clearance above unit required for air exhaust is 8 in. (203mm).
3. Keep module within 10 degrees of vertical while handling.
4. Top and bottom cable entry options available.
5. Color - black.
6. Unit bottom is structurally adequate for forklift handling.
7. M12 mounting holes used for seismic anchoring or floor stand.
8. The Primary Module includes side panels. For installations consisting of Expansion Module(s),
one side panel on the Primary Module must be removed and be placed on the end Expansion
Module.
9. Leveling feet are not designed to carry the full weight of the module.
10. Finger-tighten leveler against the floor, then tighten with a wrench less than 2 turns for friction
fit against floor.
11. Control wiring, output cabling, and input cabling must be run separately.
12. Aluminum and copper-clad aluminum cables are not recommended.
13. All wiring is to be in accordance with the NEC and applicable local codes.
NOTE
If floor stand is used, the weight of the unit must be supported under all casters.