Emerson 582145500 Power Supply User Manual


 
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
48
Section 6040
Model: NetSure™ ITM Issue AB, April 8, 2013
5. Select the "General Tab" and fill in the following:
a. System Configuration (String x Cells x Voltages): 3x8x6V.
(note that this is a pull down selection)
b. RS-485/Module Address (1-254).
For ITM Module 1, set to 120.
For ITM Module 2, set to 121.
For ITM Module 3, set to 122.
For ITM Module 4, set to 123.
c. RS-485 Baud Rate: 19200 bps.
(note that this is a pull down selection)
6. Press "Apply".