NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
57
Section 6040
Model: NetSure™ ITM Issue AB, April 8, 2013
7.0 S
PECIFICATIONS
AND
T
ECHNICAL
D
ATA
7.1 Agency Approvals
The NetSure ITM DC UPS system has the following agency approval ratings:
• EN 60 950-1:2006
• UL 60 950-1
• UL 1801 (This unit is UL Listed ["c UL"] as a DC Power Distribution Center. This unit meets the
requirements of CSA 22.2, No. 225 and is tested and Certified by UL ["c UL"] as a Custom Built
Power Distribution Center.)
7.2 Environmental
The NetSure ITM DC UPS system is designed to operate under the following environmental
conditions without damage or degradation in electrical operating characteristics:
7.3 Mechanical Characteristics
Table 7 DC UPS System Environmental Characteristics
System Operating Temperature
+23°F to +95°F (-5°C to +35°C)
Recommended Operation with Battery (Air Inlet):
+68°F to +77°F (+20°C to +25°C)
System Storage Temperature (optimal) -4°F to +77°F (-20°C to +25°C)
Relative Humidity 0 to 95%, non-condensing
Operating Elevation 6562 ft (2000m) at full power
Audible Noise < 60dB
Heat Rejection at Full Load 18,096 BTU/hr. (5.3kW) per module
EMI FCC Class A
Table 8 DC UPS System Mechanical Characteristics (per module)
Form Factor Rack
Unit Dimensions
Inches: 83H x 24W x 41D
(Millimeters: 2100H x 600W x 1040D)
Unit Weight 3240 lb (1470 kg)
Airflow 560 CFM (950 m3/h)
Cable Entry Bottom or Top
Color Black (Z-0350)
Protection Grade
(with open/closed front doors)
IP 20