NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
29
Section 6040
Model: NetSure™ ITM Issue AB, April 8, 2013
Note 1: Relay 1 through Relay 3 are defined at the factory by logic
equations factory programmed into the PLC Logic Function.
Table 4 Programmable Relay Outputs
Programmable
Relay Output
Pin No.
Alarms Assigned
to this Relay (Default)
Alarms Assigned
to this Relay (Custom)
1
J6-5 NO All alarms programmed
with alarm severity of
"critical alarm".
Relay de-energizes
during an alarm condition.
(See Note 1.)
J6-3 COM
J6-1 NC
2
J6-6 NO All alarms programmed
with alarm severity of
"warning alarm".
Relay energizes
during an alarm condition.
(See Note 1.)
J6-4 COM
J6-2 NC
3
J7-5 NO All alarms programmed
with alarm severity of
"information alarm".
Relay energizes
during an alarm condition.
(See Note 1.)
J7-3 COM
J7-1 NC
4
J7-6 NO
Available for Customer
Custom Setting
J7-4 COM
J7-2 NC
5
J8-5 NO
Available for Customer
Custom Setting
J8-3 COM
J8-1 NC
6
J8-6 NO
Available for Customer
Custom Setting
J8-4 COM
J8-2 NC
7
J9-5 NO
Available for Customer
Custom Setting
J9-3 COM
J9-1 NC
8
J9-6 NO
Available for Customer
Custom Setting
J9-4 COM
J9-2 NC