Emerson 582145500 Power Supply User Manual


 
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
15
Section 6040
Model: NetSure™ ITM Issue AB, April 8, 2013
3.4 Considerations in Moving the DC UPS Module
3.4.1 Transporting
Ensure that the DC UPS module weight is within the designated surface weight loading (lb./ft
2
or kg/
cm
2
) of any handling equipment. The DC UPS module weighs 3240 lb. (1470 kg), fully loaded.
3.4.2 Moving a DC UPS Module
Cabinet Preparation
1. Inspect the cabinet as described in 1.1 - External Inspections and 1.2 - Internal Inspections.
2. Remove the front and rear bottom panels to gain access to the bolts securing the cabinet to the
pallet.
Moving DC UPS Module from Shipping Pallet
Use lifting equipment, such as a forklift or similar equipment, appropriately rated for the weight of
the load to move the DC UPS cabinet from its shipping pallet.
When moving a DC UPS cabinet with a forklift or similar equipment, make sure that the fork is of
sufficient length for the pallet size and capable of lifting the cabinet. Also use a forklift with
adjustable forks or a narrow type.
1. Close the front door.
2. Slide the forklift into place.
3. Unbolt the cabinet from the pallet.
4. Lift the cabinet. The pallet should drop off from its own weight.
5. Carefully move the DC UPS module to its installation location or set the DC UPS module down on
its casters if it is to be rolled into position.
Moving DC UPS Module to Installation Location
The DC UPS module may be rolled on its casters when moving the unit a short distance. For longer
distances, move the DC UPS module with a forklift or similar equipment to ease the relocation and to
reduce vibration.
3.4.3 Final Positioning
Note that the DC UPS modules sit on four casters. When the DC UPS module has been finally
positioned, ensure that the adjustable stops are set so that the DC UPS module will remain
stationary and stable.
!
WARNING
Ensure that any equipment that will be used to move the DC UPS module has sufficient
lifting capacity. Ensure adequate personnel and lifting equipment are available when taking
the module off its shipping pallet. The module presents a tipping hazard. Do not tilt the
module further than 10 degrees from vertical.
The DC UPS module is fitted with casters. Take care to prevent movement when unbolting
the module from its shipping pallet. The casters are strong enough for movement across even
surfaces only. Casters may fail if they are subjected to shock loading, such as being dropped or
rolled over holes in the floor or obstructions. Such failure may cause the unit to tip over,
injuring personnel and damaging the equipment.
!
WARNING
Batteries are factory installed in the DC UPS module’s battery compartment. Care must be
taken when maneuvering modules with batteries. Keep such moves to a minimum. See
Battery Compartment Precautions on page 2.