GFK-2251 Appendix A Product Agency Approvals, Standards, and General Specifications A-3
A
General Specifications
GENERAL SPECIFICATIONS
Standard(s)
Conditions
ISOLATION
Dielectric Withstand
UL 508, UL 840,
IEC 664
1.5KV DC (input power to secondary outputs)
ENVIRONMENTAL
Vibration
IEC 68-2-6
10 - 57 Hz, 0.012" displacement peak-peak
57 - 500 Hz, 1.0g acceleration
Shock
IEC 68-2-27
15g, 11ms, sinusoidal
Operating Temperature
0°C to 50°C
Storage Temperature
-20°C to +60°C
Humidity
5% to 95% RH (non-condensing)
Enclosure Protection
NEMA 250
NEMA Type 4, 4x and 12 when mounted in panel
EMC EMISSIONS
[applies to CE Marked units]
Radiated, Conducted
CISPR 11/EN 55011
“Industrial Scientific & Medical Equipment”
(Group 1, Class A)
CISPR 22/EN 55022
“Information Technology Equipment” (Class A)
47 CFR 15
referred to as FCC part 15, “Radio Devices” (Class A)
Harmonics
EN 61000-3-2
Class D
EMC IMMUNITY
[applies to CE Marked units]
Electrostatic Discharge
EN 61000-4-2
±8KV Air, ±4KV Contact
RF Susceptibility
EN 61000-4-3
10V
rms
/m, 80Mhz to 1000Mhz, 80% AM, 1kHz sine wave
ENV 50140/
ENV 50204
10V
rms
/m, 900 ± 5Mhz, 100% PM, 200Hz square wave
Fast Transient Burst
EN 61000-4-4
±2KV: AC Input Port
±1KV: Signal Ports
Surge Withstand
EN 61000-4-5
±2KV (12Ω) CM, ±1kV (2Ω) DM: AC Input Port
±1kV (2Ω) CM: Signal Ports (shielded)
ANSI C37.90A
+2.5KV CM & DM: AC Input Port
+2.5KV CM: Signal Ports (shielded)
Conducted RF
EN 61000-4-6
10V
rms
, 0.15 to 80Mhz, 80%AM: AC Input & Signal Ports
Input Dips & Variation
EN 61000-4-11
AC Input Dips: 30 & 100% Nominal (10ms)
AC Input Variation: ±10% Nominal (10s)
Voltage Flicker
EN 61000-3-3
D
t
< 3.3%, D
c
< 3.3%, D
max
< 4.0%, P
st
< 1.0: AC Input Port