9. At the marked location of the tapped mounting holes, drill two holes approximately
1 inch to allow clearance for the ends of the two rack-mounting bolts. The ends of
the rack-mounting bolts may protrude past the thickness of the mounting plate.
Note: A minimum of three anchor bolts for each mounting plate must be used to
mount the plates to the raised-floor panel. For each mounting plate, select
at least three usable holes, two that are on opposite sides and opposite
ends of each other, and one hole at the center.
10. Drill one hole in each group of anchor bolt location marks as indicated on the
marked raised floor panel.
11. Ensure that the marks for the holes for the anchor bolts in the concrete floor align
with the holes in the raised floor panel.
12. Drill the holes in the concrete floor for the anchor bolts.
Mounting Plate (2)
Holes for Anchor
Bolts (10)
Tapped Holes for
Rack Mounting Bolts
Mounting Holes
Mounting Holes
Rack Mounting Bolts
Front of
Rack
Projection of Mounting
Plates onto Concrete Floor
Raised
Floor Panels
12 S80, S85 Installation Guide