3-2. UNIT SPECIFICATIONS
(2) Method for identifying MULTI-S model
(1) Outdoor Unit
Indoor unit < When using Model 80 >
Outdoor unit <When using model 125 >
(3) Operating temperature range
Notes D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
w1. 10~46°C DB : In case of connecting PKFY-P20/P25 type indoor unit.
P L F Y - P 80 V BM - E PU M Y - P 125 V H M A
PAC type
AM
BM
KM
M
KM
LMD
Frequency
conversion
controller
Refrigerant
R407C/R22
R410A
commonness
Refrigerant
R410A
NEW frequency converter
one-to-many air conditioners
(flexible design type)
Indicates equivalent
to Cooling capacity
(k cal / h)
Indicates equivalent
to Cooling capacity
(k cal / h)
Power supply
V: Single phase
220-230-240V 50Hz
220V 60Hz
Power supply
V: 1-phase
220-230-240V : 50Hz
220V : 60Hz
L : Ceiling cassette
K : Wall-mounted type
E : Hidden skylight type
C: Ceiling suspended type
M: Ceiling cassette type
F : Floor standing type
}
M-NET
control
Outdoor unit
model type
Sub-number Sub-number
M-NET control
Frequency
conversion
controller
Outdoor unit
MULTI-S
Service Ref.
Capacity
Cooling (kW)
Heating (kW)
PUMY-P140VHM
PUMY-P140VHMA
15.5
18.0
3.3
PUMY-P125VHM
PUMY-P125VHMA
14.0
16.0
2.9
PUMY-P100VHM
PUMY-P100VHMA
11.2
12.5
2.2Motor for compressor (kW)
Cooling
W.B. 15~24°C
D.B. -5~46°C
w1
Heating
D.B. 15~27°C
W.B. -15~15°C
Indoor-side intake air temperature
Outdoor-side intake air temperature
Cooling / Heating capacity indicates the maximum value at operation under the following condition.
w. Cooling Indoor : D.B. 27°C / W.B. 19.0°C
Outdoor : D.B. 35°C
Heating Indoor : D.B. 20°C
Outdoor : D.B. 7°C / W.B. 6°C
In case of connecting fresh air type indoor unit
air type indoor
Capacity of Fresh
Cooling
Heating
Indoor-side and Outdoor-side
P80
D.B.21~43:
w
2
W.B.15.5~35:
D.B.-10~20:
w
3
intake air temperature
P140
D.B.21~43:
w
2
W.B.15.5~35:
D.B.-5~20:
w
3
w
2.Thermo-off(FAN-mode) automatically starts if the outdoor temp. is lower than 21:D.B..
w
3.Thermo-off(FAN-mode) automatically starts if the outdoor temp. is higher than 20:D.B..