79
Header-Branch Method
Connection Examples
(Connecting to Four Indoor Units)
Liquid Line
Gas Line
Piping Diameter (mm)Model
{9.52
{15.88
Liquid Line
Gas Line
Liquid Line
Gas Line
Piping Diameter (mm)Model number
50 or lower
63 to 140
{6.35
{12.7
{9.52
{15.88
Outdoor Unit
First Branch
Indoor unit
CAP
A
B
C
D
A+a+b+c+d+e+f [ 120m
A+f [ 80m
f is 30 meters or less
30 meters or less (If the outdoor unit is lower, 20 meters or less)
12 meters or less
Please select branching kit, which is sold separately, from the table below.
(The kit comprises sets for use with liquid pipes and for use with gas pipes.)
Total Piping Length
Farthest Piping Length
Farthest Piping Length After First Branch
Height Difference in Indoor/Outdoor Section
Height
Difference in Indoor/Indoor Section
Permissible
Length
Permissible High/
Low Difference
(L)
(R)
(H)
(h)
■ Select Each Section of Refrigerant Piping
■ Selecting the Refrigerant Branch Kit
■ Additional refrigerant charge
Select the size from the right table.
(1) Refrigerant Piping Diameter in Section
From Outdoor Unit to First Branch (Out-
door Unit Piping Diameter)
(1) Section from Outdoor Unit
to First Branch (A)
(2) Sections from Branch to
Indoor Unit (a,b,c,d,e,f)
(2) Refrigerant Piping Diameter in Section
From Branch to Indoor Unit (Indoor Unit
Piping Diameter)
• Refrigerant of 3kg equivalent to 50m total
extended piping length is already charged
when the outdoor unit is shipped.
Thus, if the total extended piping length is
50m or less, there is no need to charge with
additional refrigerant.
• If the total extended piping length exceeds
50m, calculate the required additional
refrigerant charge using the procedure
shown on the right.
• If the calculated additional refrigerant charge
is a negative amount, do not charge with any
refrigerant.
<Additional Charge>
<Example> Outdoor : 125
Indoor 1 : 63 A : {9.52 30m a : {9.52 15m
2 : 40 b : {6.35 10m
3 : 25 c : {6.35 10m
4 : 20 d : {6.35 20m
The total length of each liquid line is as follows;
{9.52 : A + a = 30 + 15 = 45m
{6.35 : b + c + d = 10 + 10 + 20 = 40m
<Calculation example>
Additional
refrigerant charge = 45
✕ 0.06 + 40 ✕ 0.024 – 3.0 = 0.7kg (rounded up)
Additional
refrigerant charge
(kg)
Liquid pipe size
Total length of
{9.52 ✕ 0.06
(m) ✕ 0.06 (kg/m)
=
Liquid pipe size
Total length of
{6.35 ✕ 0.024
(m) ✕ 0.024 (kg/m)
+
Refrigerant
amount for outdoor
unit
3.0kg
–
At the conditions
below:
Branch header (4 branches)
CMY-Y64-G-E
Branch header (8 branches)
CMY-Y68-G-E
PUMY-P100-140
B
A
A
a
b
c d
C
D
CCc
CC
e f
H
h
L
r
OC376B--3.qxp 08.1.17 1:16 PM Page 79