7
4 SPECIFICATIONS
*3
*3
*3
*3
*3
*3
*3
*3
PUMY-P125VHM
PUMY-P125VHMA
Cooling Capacity kW 14.0
Heating Capacity kW 16.0
Input (Cool) kW 4.32
Input Current (Cool) A
20.0/19.1/18.3, 20.0
Input (Heat) kW 4.33
Input Current (Heat) A
20.0/19.1/18.3, 20.0
EER (Cool) 3.24
COP (Heat) 3.69
Connectable indoor units (Max.) 8
Max. Connectable Capacity kW 18.2 (130%)
Power Supply
Single phase , 50Hz 220/230/240V, 60Hz 220V
Breaker Size 32A
Sound level (Cool/Heat) dB 50 / 52
External finish Munsell 3Y 7.8/1.1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
VHM:ANB33FDCMT, VHMA:ANB33FDHMT
Model
Motor output kW 2.9
Starting method Inverter
Crankcase heater W —
Heat exchanger Plate fin coil (Anti corrosion fin treatment)
Fan Fan (drive) o No. Propeller fan o 2
Fan motor output kW 0.060 + 0.060
Airflow m
3
/min(CFM) 100 (3,530)
Dimensions (HxWxD) W mm(in.) 950(37-3/8)
D mm(in.) 330+30(13+1-3/16)
H mm(in.) 1,350(53-1/8)
Weight kg(lbs) 127(280)
Refrigerant R410A
Charge kg(lbs) 8.5 (18.7)
Protection High pressure protection HP switch
devices Compressor protection Discharge thermo, Over current detection
Fan motor protection Overheating/Voltage protection
Oil (Model) 2.3 (VHM:MEL56, VHMA:FV50S)
Total Piping length (Max.) m
L
120
Farthest m 80
Max. Height difference m 30
Chargeless length m 50
Piping diameter
Gas [mm(in) 15.88 (5/8)
Liquid [mm(in) 9.52 (3/8)
Guaranteed operation range
(cool) -5~ 46: DB
(heat) -15~ 15: WB
*1
*2
Power factor (Cool)
Power factor (Heat)
%
%
98.4
98.5
PUMY-P100VHM
PUMY-P100VHMA
11.2
12.5
3.34
15.4/14.8/14.1, 15.4
3.66
16.9/16.2/15.5,16.9
3.35
3.42
6
14.5 (130%)
49 / 51
2.2
98.4
98.4
PUMY-P140VHM
PUMY-P140VHMA
15.5
18.0
5.35
24.7/23.6/22.7,24.7
5.58
25.8/24.7/23.6,25.8
2.90
3.23
8
20.2 (130%)
51 / 53
3.3
98.4
98.4
Rating conditions (JIS B 8616)
Cooling Indoor : D.B. 27: / W.B. 19:
Outdoor : D.B. 35: / W.B. 20:
Heating Indoor : D.B. 20:
Outdoor : D.B. 7: / W.B. 6:
Note. *1. 20m :In case of installing outdoor unit lower than indoor
unit.
*2. 10~46:DB :In case of connecting PKFY-P20/P25 type indoor
unit.
*3. Electrical data is for only outdoor unit.
OC376B--1.qxp 08.1.17 1:14 PM Page 7