Multi-Tech Systems 7500 Network Card User Manual


 
Event Logging ION 7500 / ION 7600 User’s Guide
Page 150 Chapter 5 - Features and Applications
Event Logging
Events produced by a meter’s various ION modules are prioritized and grouped
to facilitate custom logging. Each event is assigned a priority group number based
on its type and severity.
ION Event Priority Groups
Some event groups are preset with a Priority Number as shown in the table below.
You can also define your own priority number for some modules. Priority
numbers from 128-191 appear in the global even log viewer in ION Enterprise
software. Priority numbers from 192-255 are logged, initiate a beep and cause the
window to flash. You can customize these responses to display messages or
perform netsend messages, for example.
The Event Log Controller module allows you to set a priority cutoff for event
logging. Any events with a priority number greater than the cutoff value are
logged, and events with lower priorities are discarded. Refer to the individual
module descriptions and the Event Log Controller module description in the
online ION Programmer’s Reference for more details.
Event Group Description Priority Number
Reset Module reset or re synchronized 5
Setup Change Module setup changes (setup register changes, label changes, input handle changes) 10
Input Register Change Inputs of certain modules change value (ie, input to And/Or module changes) 15
I/O State Change I/O state changes (ie, relay closes) 20
Information Module produces important user information 25
Warning Module produces a warning 30
EN50160 Event
(ION 7600 only)
An EN50160 Counter (N
1
or N
2
) increases
50
Failure A failure has occurred 255
Setpoint Setpoint condition goes Active or Inactive (ie, Sag/Swell module detects a disturbance)
programmable via
module setup