Multi-Tech Systems 7500 Network Card User Manual


 
Mains Signaling Voltage ION 7500 / ION 7600 User’s Guide
Page 322 Power Quality: ION Meters and EN50160 Technical Note
Mains Signaling Evaluation Module Settings
To enable EN50160 mains signal voltage monitoring, you must specify the signal
frequency of interest and the allowable signal voltage threshold for each of the
three voltage phases. These parameters are held in the Frequency and Limit setup
registers of their respective Mains Signaling Evaluation modules.
The allowable Frequency range is 5 Hz to 2500 Hz (default is 1060 Hz). If this
register is set to 0Hz, then no evaluation will be performed. The voltage threshold
defined by the Limit setup register must be expressed as a percentage of the
fundamental (default is 100%). Refer to the online ION Programmer’s Reference for
more details about this module.
Mains Signaling Default Measurements
* This data is recorded weekly by Data Recorder 31.
Register Label Source Module Description
V1-MSignal N*
Mains Signalling
Evaluation
number of valid intervals (voltage on phase 1 within +/- 15% of nominal)
V1-MSignl N ivd* number of invalid intervals
V1-MSignal N1* number of valid intervals in which the signaling voltage on phase 1 exceeds a user defined limit
V2-MSignal N* number of valid intervals (voltage on phase 2 within +/- 15% of nominal)
V2-MSignl N ivd* number of invalid intervals
V2-MSignal N1* number of valid intervals in which the signaling voltage on phase 2 exceeds a user defined limit
V3-MSignal N* number of valid intervals (voltage on phase 3 within +/- 15% of nominal)
V3-MSignl N ivd* number of invalid intervals
V3-MSignal N1* number of valid intervals in which the signaling voltage on phase 3 exceeds a user defined limit
PO V1-MSignal N
Store
PO V1-MSignal N of the previous Observation Period
PO V1-MSgnal N1 PO V1-MSgnal N1 of the previous Observation Period
PO V2-MSignal N PO V2-MSignal N of the previous Observation Period
PO V2-MSgnal N1 PO V2 MSgnal N1 of the previous Observation Period
PO V3-MSignal N PO V3-MSignal N of the previous Observation Period
PO V3-MSgnal N1 PO V3-MSgnal N1 of the previous Observation Period
V1-MSig N1/N
Arithmetic
N1/N ratio
V2-MSig N1/N N1/N ratio
V3-MSig N1/N N1/N ratio
PO V1-MSig N1/N N1/N ratio of previous Observation Period
PO V2-MSig N1/N N1/N ratio of previous Observation Period
PO V3-MSig N1/N N1/N ratio of previous Observation Period