Multi-Tech Systems 7500 Network Card User Manual


 
Description of KCTSTP and KCTRD Calibration Commands ION 7500 / ION 7600 User’s Guide
Page 190 Current Probe Inputs Basic Setup Technical Note
KCTRD
Read all current probe setup registers
Description:
This command lists the content of all current probe setup registers. There are three
identical groups of registers: Factory Default (configured in the factory), User
Defined 1, User Defined 2 (both for user configuration).
Each group contains the following probe parameters:
Primary Nominal Current, Secondary Nominal Voltage, Probe Name Tag
(character string). Additionally, if the meter was ordered with factory calibrated
current probes, then the Factory Default register group contains probe phase
compensation coefficients.
For meters equipped with Current Probe Input Option, but not ordered with
factory calibrated current probes, all register groups should contain zero values,
except for Nominal Current and Voltage, which are set to 1.0 by default.
For meters NOT equipped with Current Probe Input Option, all register groups
should contain zero values, except for Nominal Current and Voltage, which are set
to 1.0 by default.
Arguments:
None