Powerware 5075 kVA Power Supply User Manual


 
NOTE:
Callout letter and
map to drawing #164201261---3
,,,
DESCRIPTION:
DATE:
DRAWING NO:
2of11
INSTALLATION NOTES
SHEET:
REVI SION:
F
111503
164201261---1
A---3
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
Table B. OUTPUT Ratings & External Wiring Requirements for
Powerware BPIII HE 50---75 kVA (208 and 480 Volt)
Ratings
Units Rating 60 Hz
Basic unit rating at
0.8 lagging PF load
KVA
KW
50
40
62.5
50
75
60
g
g
g
OUTPUT
VOLTAGE
208 480 208 480 208 480
A
C
O
AC Output to Critical Load
Full Load Current3
, (1) Neutral, (1) gnd
Amps (Nom) 139 60 175 75 208 90
O
U
T
P
U
T
Minimum conductor size
(number per )
AWG or
kcmil(ea)
3/0
(1)
4
(1)
350
(1)
2
(1)
350
(1)
1
(1)
7. The output of the UPS is a separately derived source. Output neutral is bonded to
equipment ground through the main bonding jumper. Refer to NEC Article 250 and local
codes for proper grounding practices.
8. External overcurrent protection is not provided by this product, but is required by codes.
Refer to Table A through C for wiring requirements. If external overcurrent protection or an
output lockable disconnect is required, it is to be supplied by designated personnel.
9. Non-linear loads can create neutral currents that are greater than 100%. This product can
accommodate double-sized neutral terminations if needed.