RuggedCom RSG2288 Switch User Manual


 
Installation
2.3.3 Dual Power Supplies – DC and AC Inputs
Figure 20: DC and AC Power Supply Wiring Examples
Notes:
125/250VDC rated equipment: A 300VDC appropriately rated circuit breaker
must be installed.
100-240VAC rated equipment: A 250VAC appropriately rated circuit breaker
must be installed.
A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.
Separate circuit breakers must be installed and separately identified.
Equipment must be installed according to the applicable country wiring
codes.
23
RuggedCom
®
RuggedSwitch
®
RSG2288 Installation Guide rev103