Schneider Electric INTERBUS Basic Network Interface Module Computer Hardware User Manual


 
Configuring the Island Bus
890USE19600 April 2004 31
An Example For example, if you have an island bus with eight I/O modules:
1 NIM
2 STB PDT 3100 24 VDC power distribution module
3 STB DDI 3230 24 VDC two-channel digital input module
4 STB DDO 3200 24 VDC two-channel digital output module
5 STB DDI 3425 24 VDC four-channel digital input module
6 STB DDO 3415 24 VDC four-channel digital output module
7 STB DDI 3615 24 VDC six-channel digital input module
8 STB DDO 3605 24 VDC six-channel digital output module
9 STB AVI 1275 +/-10 VDC two-channel analog input module
10 STB AVO 1255 0 ... 10 VDC two-channel analog output module
11 STB XMP 1100 island bus termination plate
The NIM would auto-address it as follows. Note that the PDM and the termination
plate do not consume island bus addresses:
Module Physical Location Island Bus Address
NIM 1 127
STB PDT 3100 PDM 2 not addressed—does not exchange data
STB DDI 3230 input 3 1
STB DDO 3200 output 4 2
STB DDI 3425 input 5 3
STB DDO 3415 output 6 4
STB DDI 3615 input 7 5
STB DDO 3605 output 8 6
STB AVI 1275 input 9 7
STB AVO 1255 output 10 8