Sharp JW-21MN Network Card User Manual


 
16-16
(2) Parameter setting by remote function
This paragraph describes how to set the parameters of other stations' network module (JW-21MN/
JW-20MN) connected on the ME-NET. This is only available when the target station is within the
standard network connection.
Usable support tools are JW-14PG/13PG/12PG.
< An operation example using the JW-14PG >
Connect the programmer to the JW-21MN
on the ME-NET.
Select initial mode.
Assign the parameter setting remotely.
Select "LINK" in initial.
Select display mode of "1PG, 2PG1 MODE" in specified link.
Select target station." in 1PG, 2PG1 MODE.
Select the target station to set the parameter remotely.
Change the code from hexadecimal(H) display to octal(O) display and input the target
station (00(8) to 77(8)).
Communication with the target station.
Initiate communication with the target station.
After finishing communication with the target station, set the parameters remotely.
Return to initial menu.
- Turn the PC of the target station to program mode (stop PC operation).
- Select "PARAM." in the initial mode.
Display the contents of parameter address
007777(8).
Write 00(H) to stop operation of the JW-21MN.
(Input address) (Enter the set value)
Display the contents of the address and then set the parameters.
Write 81(H) in parameter address 007777(8), and then write the parameter contents into the
EEPROM of the JW-21MN. Then start operation of the JW-21MN.
(3) Compatible with file register for file 10 to 2C (compatible with the JW-33CUH2/3)
1) When used with a data link
[File 10 to 2C(H)] (SEG10 to 2C) can be assigned as the top address of the register link area and
flag range.
2) When used with a computer link
[File 10 to 2C(H)] (SEG10 to 2C) can be used to read the current register value (command 24(H)),
write to a register (command 34(H)), or write to the same data register (command 35(H)).
(JW-21MN)
Display initial mode.