Sharp JW-21MN Network Card User Manual


 
11-25
Turn to program mode (stop PC operation). Setting of parameters is only available when the PC is
in program mode.
Select parameter setting mode.
Write "00(H)" to parameter address 007777(8) and stop operation
of the JW-21MN. Setting of the parameter is only available
when the operation of the JW-21MN is stopped.
Connect a support tool with the JW-21MN.
<Usable support tools>
JW-14PG/13PG/12PG
JW-50SP
JW-50PG, Z-100LP2S
- For operation of each support tool, see the instruction
manual attached. The following describes an example
of JW-14PG's key operation.
Note: Setting parameters is unavailable by JW-2PG.
(JW-14JG)
JW-21MN
007777(8)
0 0(H)
Indications in [ ] of each item mean as follows:
(Example) Stop operation of data link [HEX (hexadecimal), byte]
This means to set "stop operation" by hexadecimal and byte unit.
Turn "ON" the power of slave station PC
Connect support tools
Stop PC operation
Stop operation of data link [HEX (hexadecimal), byte]
Stop PC operation
Select initial mode
Display the contents of parameter
address 007777 by hexadecimals.
Reference
Function of JW-14PG
To the next page
Screen display of JW-14PG
07775 HEX 00
07776 HEX 1F
I PARAM.
>07777 HEX 00
Write
00
(H).
(Set parameter)
- key: Changeover unit of figures
HEX (hexadecimal)
OCT (octal)
DCM (decimal) Bit pattern
- key: Byte display Changeover word display