Sierra 240-VTP Network Router User Manual


 
Chapter 3 Operation Series 24-HP Instruction Manual
3-10 IM-24-HP
Energy Menu – For EMS Energy Meters Only
Password
ENTER
Use
keys to access menus
Energy
Menu
Loc in Sent
Flow
Yes or No
ENTER
Run Mode
Heating
System
Yes or No
% Returned
xxx
Configuration:
There are several possibilities regarding the measurement of water or steam energy given the location
of the meter and the use of a second RTD. The table below summarizes the possibilities:
Fluid Meter Location Second RTD Measurement
Water “Sent” Flow Line “Return Flow Line Change in Energy
Water “Return” Flow Line
“Sent” Flow Line Change in Energy
Water “Sent” Flow Line None Outgoing Energy
Steam “Sent” Flow Line “Return” Flow Line
(condensate)
Change in Energy
Steam “Sent” Flow Line None Outgoing Energy
As above, you must properly configure the meter in the Energy Menu.
1. Loc in Sent Flow? Select Yes or No based on where the meter is located. Refer to the above
table
2. Heating System? Select Yes for a hot water system used for heating. Select No for a chilled
water system used for cooling. Always select Yes for a steam system.
3. % Returned. Select a number between 0% and 100%. Estimate the amount of water that returns.
It is usually 100%, or can be less than 100% if historical data shows the amount of makeup water
used. If a second RTD is not used, set to 0%. When 0% is selected, the energy calculation
represents the outgoing energy only (no return energy is subtracted). NOTE: the meter ships
from the factory assuming 0% return and has a 1000 ohm resistor installed in the RTD #2
wiring location. This needs to be removed if the meter is to be used in a manner other than
with 0% return and with the customer supplied RTD in its place.