78 XLi IEEE 1588 Clock
997-01510-03, Rev. C, 12/12/2006
SSSSSSSSSSSS SSSSSSSSSS SSSSSSS S SSS S SSSSS S
1
Command Line
To display the current settings, enter:
F74<CR>
XLi responds, using the following format:
F74<S><CLK SOURCE><CR><LF>
where:
For example, enter:
F74<CR>
XLi responds (example):
F74 PRI<CR><LF>
To select PRI-SEC-SEC as the new clock source/fail-over pattern, enter:
F74 PRI-SEC-SEC<CR>
XLi responds:
OK<CR><LF >
F90 – Code Output Configuration
Use function F90 to configure the time code output format (IRIG-A, IRIG-B, or NASA 36) and modulation
type (AM or DC) on the XLi’s standard CODE output.
F = ASCII character F.
74 = function number.
<S> = Space
<CLK SOURCE> = Clock Source:
•PRI
• SEC
• PRI-SEC-SEC
• PRI-SEC-PRI
• PRI-NSEC-PRI
<CR> = carriage return character.
<LF> = line feed character.