Block Write 1, 2
Select data, which is desired to be written in block communications, in Block Communication Write
Data 1 and 2 Parameters (, ). This parameter becomes effective when the system
is reset, such as when power is turned off. When the setting is completed, turn off and then on the
power.
* When “No selection” is specified in the parameters, no data will be written even though write data is
specified.
Block Read 1 to 5
Select read data, which is desired to be read in block communications, in Block Communication
Read Data 1 and 5 Parameters (to). This parameter becomes effective when
the system is reset, such as when power is turned off. When the setting is completed, turn off and
then on the power.
* Output current (FE03), output voltage (FE05) and PID feedback value (FE22) will become hold data
during a trip. Otherwise, real-time data appears.
* “0000” will be returned as dummy data, if “0 (No selection)” is selected for the parameter and “read”
is specified.
No. Block Write Data For data details, see:
0 No selection
1 Command 1 (FA00) “8.1 Command by communication”
2 Command 2 (FA20) “8.1 Command by communication”
3 Frequency Command Value (FA01) “8.1 Command by communication”
4 Terminal Board Output Data (FA50)
“8.3 Control of input/put signals from com-
munication”
5 Communication Analog Output (FA51)
“8.3 Control of input/put signals from com-
munication”
No. Block Read Data For data details, see:
0 No selection
1 Status 1 (FD01) “8.2 Monitoring from communication”
2 Output Frequency (FD00) “8.2 Monitoring from communication”
3 Output Current (FE03) “9. Parameter data”
4 Output Voltage (FE05) “9. Parameter data”
5 Alarm Information (FC91) “8.2 Monitoring from communication”
6 PID Feedback Value (FE22) “9. Parameter data”
7 Input Terminal Board Monitoring (FD06)
“8.3 Control of input/put signals from
communication”
8 Output Terminal Board Monitoring (FD07)
“8.3 Control of input/put signals from
communication”
9 Analog Monitoring VIA (FE35)
“8.3 Control of input/put signals from
communication”
10 Analog Monitoring VIB (FE36)
“8.3 Control of input/put signals from
communication”