4.5. Examples of the use of communication commands
Here are some examples of the use of communications commands provided for the VF-S11 series of
inverters.
Inverter numbers and checksum used in ASCII mode are omitted from these examples.
Examples of communications
- To run the motor in forward direction with the frequency set to 60 Hz from the computer
<ASCII mode>
Computer Inverter Inverter Computer
(PFA011770)CR (PFA011770)CR …Set the operation frequency to 60 Hz.
(60 / 0.01 Hz = 6000 = 1770H)
(PFA00C400)
CR (PFA00C400)CR …Set to “forward run” with commands and frequency
instruction from the computer enabled.
<Binary mode>
Computer Inverter Inverter Computer
2F 50 FA 01 17 70 01 2F 50 FA 01 17 70 01
2F 50 FA 00 C4 00 3D 2F 50 FA 00 C4 00 3D
- To monitor the operation frequency (during 60 Hz operation)
<ASCII mode>
Computer Inverter Inverter Computer
(RFD00)CR (RFD001770)CR …Set the operation frequency to 60 Hz.
(60÷0.01Hz=6000=1770H)
<Binary mode>
Computer Inverter Inverter Computer
2F 52 FD 00 7E 2F 52 FD 00 17 70 05
- To monitor the status of the inverter
<ASCII mode>
Computer Inverter Inverter Computer
(RFD01)CR (rFD010003)CR …For details on statuses, see 8.2 “Monitoring from
the computer.” (Stop status, FL output status, trip
status (r command))
<Binary mode>
Computer Inverter Inverter
Computer
2F 52 FD 01 7F 2F 72 FD 01 00 03 A2
- To check the trip code (when the inverter is tripped because of )
…For details on trip codes, see “Trip code monitor” in 8.2, “Monitoring
from the computer.” (18H = 24d “” trip status)
<ASCII mode>
Computer Inverter Inverter
Computer
(RFC90)CR (rFC900018)CR
<Binary mode>
Computer Inverter Inverter
Computer
2F 52 FC 90 0D 2F 72 FC 90 00 18 45