Toshiba TOSVERT VF-S11 Power Supply User Manual


 
E6581222
39
6.2. Transmission format for inter-drive communication
Data type is handled in hexadecimal notation and the transmission characters are treated with the
binary (HEX) code.
The transmission format is basically the same to the case of binary mode. S command is used and
the slave inverters do not return the data.
Master inverter (VF-S11) to slave inverter (VF-S11) (Binary mode)
(2FH)
INV-NO
1 byte
CMD
1 byte
Communication number
2 bytes
DATA
2 bytes
SUM
1 byte
1) INV-NO (1 byte) : Inverter number
This is always excluded at the master inverter side at time of inter-drive communication, and
can be added when the user utilize this data for the purpose of proportional operation.
(When this code is added, only the inverter concerned will accept the data.)
2) CMD (1 byte) : Command
53H(“S”) or 73(“s”) command ... command for inter-drive communication
When the master inverter is not tripping, this will be 53H(“S”).
When the master inverter is tripping, this will be 73H(“s”).
3) Communication number (2 bytes) :
Communication number of frequency command (FA01).
4) DATA (2 bytes) : Data of frequency command value.
(0000H to FFFFH (no range check))
As for the S command, see section 4.2 “Commands”, and see chapter “6 Inter-drive communication function” for the
communication of inverters.
Checksum range
Not omissible
Omission