Toshiba TOSVERT VF-S11 Power Supply User Manual


 
E6581222
61
Command parameters
For those parameters that contain data only in the RAM and not in the EEPROM, their data return to
initial values when the power is turned off, in failure resetting, or when standard shipment settings
are set. Note that parameters without data storage in the EEPROMs will be written in the RAMs
only even if the command W (writing in EEPROMs and RAMs) is executed.
Commands
                         NOTE : Data is expressed in decimal notation.
C
ommunica
-
tion
Num-
ber.(HEX)
Function
Adjustment Range
Min.
Setting
Unit
Initial
Value
Write
During
O
pe
r
atio
n
EEP
ROM
FA00 Command 1 (Communication)
1
0 to 65535 0 yes None
FA01 Operation frequency command
value (Communication)
1
0 to Max. frequency
(
)
0.01Hz 0 yes None
FA03 Operation frequency command
value (Panel)
2
Low-limit frequency
(
) to High-limit
frequency (
)
0.01Hz 0 yes Available
FA10
Panel key selection
4
0 to 1 0 yes None
FA11 External communication key
data
4
0 to 65535 0 yes None
FA20 Command 2 (Communication)
1
0 to 65535 0 yes None
FA26 Command 3 (Communication)
1
0 to 65535 0 yes None
FA50
Terminal output data
3
0 to 65535 1 0 yes None
FA51
Analog output data
3
0 to 1023
(10-bit resolution)
1 0 yes None
FA65 Select display by communica-
tion
4
0 to 2 1 yes Available
FA66
Numerical display data
4
0-9999 1 0 yes Available
FA67
Decimal point position
4
0 to 2 0 yes Available
FA68
LED data for unit 0
4
0 to 3 0 yes Available
FA70 ASCII display data 1
First digit from left
4
0 to 127 100
(‘d’)
yes Available
FA71 ASCII display data 1
Second digit from left
4
0 to 255 65
(‘A’)
yes Available
FA72 ASCII display data 1
Third digit from left
4
0 to 255 116
(‘t’)
yes Available
FA73 ASCII display data 1
Fourth digit from left
4
0 to 127 65
(‘A’)
yes Available
FA74
LED data for unit1
4
0 to 3 0 yes Available
FA75 ASCII display data 2
First digit from left
4
0 to 127 48
(‘0’)
yes Available
FA76 ASCII display data 2
Second digit from left
4
0 to 255 48
(‘0’)
yes Available
FA77 ASCII display data 2
Third digit from left
4
0 to 255 48
(‘0’)
yes Available
FA78 ASCII display data 2
Fourth digit from left
4
0 to 127 48
(‘0’)
yes Available
FA79
LED data for unit 2
4
0 to 3 0 yes Available
FA80
Block communication mode
4
0 to 1 0 yes Available
1
: Enable the communication command or communication frequency setting before setting these
parameters are set. Otherwise, the parameters will not function. See “8.1 Command by com-
munication” for the method to enable them.
2
: Note that the Communication Number for operation frequency command values (panel) is FA02
in the VF-S7 and VF-S9 series.
3
: See “8.3 Control of input/output signals from communication” for the detail information.
4
: See “8.4 Utilizing panel (LEDs and keys) by communication” for the detail information.