E6581222
60
9. Parameter data
Explanation of parameters for VF-S11 series is described here. For communication purposes, see
the parameter list on inverter's instruction manual regarding the communication number, adjustment
range and so forth.
■ Referring to the parameter list
<Example of excerpts from the inverter’s instruction manual>
Title
Com-
munica-
tion No.
Function unit
Minimum
setting unit
Panel/Com
munication
Adjustment range
Default
setting
User
setting
Reference
auh
- History function - -
Displays parameters in
groups of five in the reverse
order to that in which their
settings were changed.
* (Possible to edit)
-
4.1.4
0000
Automatic ac-
celera-
tion/deceleration
--
0: Disabled (manual)
1: Automatic
2:Automatic (only at accelera-
tion)
0 5.1.1
0001
Automatic tor-
que boost
--
0:Disabled
1:Automatic torque boost +
autotuning
2:Vector control + auto-tuning
3:Energy saving + auto-tuning
05.2
0009
Acceleration
time1
S 0.1/0.1 0.0-3200 10.0 5.1.2
- The summary of parameter list relating to the communication is as follows.
(1) “Title” means the display on the inverter panel.
(2) “Communication number” is affixed to each parameter that is necessary for designating the parameter for com-
munication.
(3) "Adjustment range" means a data range adjustable for a parameter, and the data cannot be written outside the
range. The data have been expressed in the decimal notation. For writing the data through the communication
function, take the minimum setting unit into consideration, and use hexadecimal system.
(4) "Minimum setup unit" is the unit of a single data (when the minimum unit is "-", 1 is equal to 1).
For example, the "minimum setup unit" of acceleration time () is 0.01, and 1 is equal to 0.01s. For setting a
data to 10 seconds, transmit 03E8h [10
0.01=1000d=03E8h] by communication.