2.3 TECHNICAL DATA
Type rating
Protect D. 6000 6000 VA (cos ϕ = 0.9 lag) 5400 W
Protect D. 10000 10000 VA (cos ϕ = 0.9 lag) 9000 W
UPS input 1ph~ / N / PE (DUAL INPUT)
Nominal input voltage 200 / 208 / 220 / 230 / 240 Vac
Rectifier voltage range
(without battery operation,
100% load, cos ϕ = 0.9 lag)
176 Vac – 276 Vac
Rectifier voltage range
(without battery operation
50% power reduction)
120 Vac – 276 Vac
Bypass voltage range 184 Vac – 264 Vac
Frequency 50 Hz / 60 Hz (automatic detection or manually)
Frequency tolerance range ± 10%
Charging rate at full load
and battery charging (max.)
Protect D. 6000 29 A (U
N
=230 Vac)
Protect D. 10000 47 A (U
N
=230 Vac)
Circuit feedback factor λ ≥ 0.99 (THDi <5%)
UPS output
Nominal output voltage 200 / 208 / 220 / 230 / 240 Vac ± 1%
Power reduction at 200 Vac
Nominal output voltage: 10%
Nominal frequency 50Hz / 60Hz ± 0,5% (Tolerance in battery mode
or free running in frequency changer mode)
Synchronization range 50Hz or 60Hz ± 10%
Synchronization speed 1 Hz / s
Power factor range 0.5 lag to 0.9 cap. at full power output
Power reduction: 20% to 0.5 cap.
Frequency converter 20% power reduction
(Bypass deactivated, frequency range 40 – 70 Hz)
Waveform Sinus, distortion < 2% THD (linear load)
< 5% THD (non-linear load)
Crest factor 3:1