54
The “UPS on Battery” notice and the “Battery Low” alarm do not activate during
a battery test.
A battery test can only be run under the following conditions:
• The UPS must be in Normal mode
• There can be no active alarms
• The batteries must be fully charged.
• The input voltage with respect to the bypass voltage window must be within
tolerance range
Description Adjustable parameters Presetting
High ambient
temperature alarm
[enabled], [disabled]
Preset alarm threshold at > 40 °C
enabled
EPO operation [normally open], [normally closed]
Normally open means UPS makes a
shutdown by a closing input state.
Normally closed means UPS makes a
shutdown by an opening input state.
Setting only available in UPS stand-by mode.
normally
closed
Reset Cumulative
Consumption kWh
[no], [yes]
If “no”, no action.
If “yes”, the Cumulative Consumption kWh
value is cleared and the date and time stamp
for this statistic is set to the current date and
time.
no
Limitations of
battery usage
5h, 6h, ...14h, 15h, 16h, …999h, inactive
If the selected time window for UPS battery
operation is exceeded, the UPS will make
bat low alarm and then shut itself down 30
minutes later even if battery voltage is still
above the shutdown value.
Disabled means “No time limitation” for
battery mode
14h