12
Overload behavior
with existing network
To 102% continuously;
≥ 102% – <130% for 2 min.
≥ 130% – <150% for 30 s
Automatic seamless transfer to bypass mode (SBS)
Overload behavior
Bypass
to 130% continuously;
≥ 130% – <180% for 1 min.
Overload behavior
when on battery
to 102% continuously;
≥ 102% – <130% for 10 s
≥ 130% for 100 ms
Short circuit protection 3 x I
N
for 100 ms
Battery
Autonomy time
Coupled
battery module
(cos ϕ = 0.9 lag / 100% charged battery / 25°C)
D. 6000
(rated load)
D. 6000
(half load)
D. 10000
(rated load)
D. 10000
(half load)
with integrated battery 3 min. 9.5 min. 4 min. 7.5 min.
1 add. battery module 11 min. 27 min. 9 min. 18 min.
2 add. battery modules 20 min. 46 min. 15 min. 30 min.
3 add. battery modules 30 min. 68 min. 21 min. 43 min.
4 add. battery modules 40 min. 91 min. 27 min. 57 min.
Battery check
(programmable):
Daily, weekly, monthly
Rated DC voltage
(DC Link)
Protect D. 6000 180 Vdc
Protect D. 10000 240 Vdc
Float voltage 2.28 Vdc / cell (default 20°C)
Charging voltage depending on temp.
Adjustment 2.21 Vdc / cell – 2.31 Vdc / cell in 0.01 V increments
Temperature compensation 20m V / 12 V-Block / °C
Battery charging current
(max.)
1.4 Adc (Protect D. 6000)
1.7 Adc (Protect D. 10000)
Switch-off
1.60 to 1.75 V / cell (load and temperature
dependent)