AEG 6000BP Power Supply User Manual


 
52
Description Adjustable parameters Presetting
Audible Alarms [enabled], [disabled]
NOTE. The setting takes place immediately
and will remain permanently stored, even in
the case of power failures.
This differs from the mute feature where the
horn is temporarily silenced on any button
press, but turns on again if a new alarm is
triggered.
enabled
Set Date and Time Set Month, Day, Year, Hours and Minutes;
Date layout: mm / dd / yyyy
Time layout: hh:mm
NOTE: The date format depends on the
language selection.
NOTE: Time is a 24-hour clock.
03 / 15 / 2010
18:00
Relay configuration [UPS ok], [on bypass],
[on economical mode (ECO)],
[on battery], [battery low],
[battery fault], [battery missing],
[fan fault], [combined alarm]
UPS ok
Control Commands
from Serial Port
[enabled], [disabled]
If Enabled, control commands are
accepted through Serial & USB port
and cards in the communication slot.
If Disabled, configuration and load control
commands are restricted to LCD panel only.
enabled
Output Voltage [200V], [208V], [220V], [230V], [240V],
[auto-sensing]
Setting only available in UPS stand-by mode.
auto-sensing
Output Frequency [50Hz], [60Hz], [auto-sensing]
Setting only available in UPS stand-by mode.
auto-sensing