AEG 6000BP Power Supply User Manual


 
49
Battery status display Description
Battery charge Batteries are currently charging with constant
current.
Battery float charge Batteries are currently being supplied with constant
voltage.
Battery resting Batteries on standby, but in “sleep” mode
(part of the battery standby cycle mode).
Battery discharge Batteries are currently discharging, e.g. due
to a power outage.
Battery disconnected Battery system not available because currently not
connected.
7.3.2 EVENT LOG
Up to 127 events are stored in the internal non-volatile event memory in the UPS.
The last event that occurred is the first on the list, followed by other previous
events. Similar to the messages and alarms, each event is shown in its own
window.
An event is indicated along with the date and time, followed by a description in
plain text. The numerical code facilitates error analysis and other procedures in
dealing with the event that has occurred (also see chapter 9.1.1 from page 61). In
the lower right-hand corner of the display, you will find the total number of events
already stored as well as your position when scrolling through the window. “1 / …”
indicates the most recent, last stored event (= starting position when accessed).
If there are no events stored or if the event memory has been deleted (also see
chapter 7.3.6 from page 51), the following message will appear: “No events in the
event log”.
ACCESSING THE EVENT LOG
Access the event log by pressing “ESC” to go to the main menu and then
pressing “” or “” to go to the “Event log” menu item (line appears
highlighted) and then press “ENTER” (basis / starting point is the UPS status
display).
Return to the UPS status display by pressing “ESC” again (or automatically
after 5 minutes if no other keys are pressed).