Battery voltage Visual and audible alarm at 1.90 V / cell
Type of battery Sealed lead-acid battery (VRLA)
spec. type for high-current discharge
Protect D. 6000 15 blocks at 12 V 5 Ah
Protect D. 6000 BP 15 blocks at 12 V 9 Ah
Protect D. 10000 20 blocks at 12 V 9 Ah
Protect D. 10000 BP 20 blocks at 12 V 9 Ah
Recharging times ~ 3h to 90% for internal battery
~9h / ~15h / ~21h / ~27h with 1 / 2 / 3 / 4 battery
extension(s)
Communication
Interfaces
(DUAL Monitoring)
RS232 (SUB-D (9-pin)), USB
Additional: communication slot for extensions
(e.g. relay card / SNMP (PRO), etc.)
EPO contact Potential-free
(optionally programmable as opener or closer)
Relay load-carrying ability 250 Vac 3 A or 30 Vdc 3 A change-over contact
(programmable)
Shutdown software on CD “CompuWatch” for all popular operating systems,
inc. Windows, Linux, Mac, Unix, Novell, Sun
General information
Classification VFI SS 111 acc. to IEC 62040–3
Double-conversion technology
Full-load efficiency
(AC-AC / DC-AC)
Protect D. 6000
Protect D. 10000
> 92% / >89%
> 93% / > 90%
Full-load efficiency
(ECO / transfer time < 10ms)
Protect D. 6000
Protect D. 10000
> 96%
> 97%
Inherent noise (1m distance) <55 dB(A)
Cooling External variable-speed cooling fan
Operating temperature range 0°C bis +40°C
Recommended: +15°C to +25°C
(battery system dependent)
Storage temperature range -15°C to + 60°C (UPS)
0°C to + 35°C (battery)