4.2 INSTALLATION
The Protect D. is designed to be installed in a protected environment. When
choosing the location, make sure that there is adequate ventilation and any other
environmental requirements deemed appropriate.
The Protect D. is air-cooled. Do not block vents or openings!
The UPS and its battery modules in particular, should preferably be operated at
room temperature (between 15°C and 25°C).
Install the devices in a room that is dry, relatively dust-free and free of chemical
vapors.
Make sure that no magnetic storage media are stored and / or operated in the
vicinity of the Protect D.
Check the type rating plate to make sure that the voltage and frequency
specifications match those of your load segments.
4.3 ASSEMBLY
For rack installation of the UPS system and its external battery units (Optional
accessories), please note the following:
• To prevent damage from vibration and shocks, the installation location has
to have adequate stability.
• Make sure that racks are able to support the installation.
• Place any external battery units directly underneath the UPS system.
To ensure maximum mechanical stability, place each tray in its own rack mount.
• Due to their heavy weight, install the units in the lower part of the cabinet.
• Install the units allowing for adequate air circulation.
• External battery packs are to be placed directly below the UPS system.
To maintain maximum mechanical stability, mount each tray on a pair of
separate rack rails.
• Avoid extremes of temperature! In order to maximize battery life, an
environmental temperature of 15°C to 25°C is recommended. Do not expose
the units to direct sunlight or operate them close to any other heat sources,
e.g. radiators.