AEG 6000BP Power Supply User Manual


 
36
A flashing LED in conjunction with a fault signal indicates a disconnection fault.
Follow the instructions in chapter 9.1
Finally check the seating of the emergency shutdown connector and the cable
bridge. Check that the two outer screws of the plug are firmly seated (refer to
page 30 item 11)
If you would like to use the emergency function, refer to chapter 8.4 on page 58.
The built-in emergency shutdown of the UPS is only for power. This is carried out
electronically and does not constitute an EMERGENCY STOP device according to
DIN EN ISO 13850.
6.4 CONTACTING THE BATTERY MODULES
This chapter refers to the contact of the internal battery and then to a slide-on
connection of the optional external battery pack(s)
6.4.1 CONNECTING THE INTERNAL BATTERY
• Remove the four screws on the front panel with a suitable screwdriver (Phillips
PH1 recommended Item “E” of the illustration on page 26)
• Hold the Protect D. 6000 on the left and right sides behind the front panel and
carefully pull the UPS out about 70mm from the front of the rack frame (not
required with Protect D. 10000)